Product Handbook 2026 - Volume 1

Control systems Pressure reducing/surplussing valves

4

Safety information, installation and maintenance For full details see the Installation and Maintenance Instructions (IM-S12-10) supplied with the product. Installation note: Caution - To protect the actuator diaphragm on steam applications a WS4 series water seal pot must be installed in the upstream pressure signal line to the actuator. Refer to TI-S12-03 for details. The valve should be mounted vertically downwards in a horizontal pipeline with the direction of flow as indicated by the arrow on the valve body. For applications with downstream temperatures below 125 °C the valve can alternatively be mounted vertically upwards.

How to order Example: 1 off Spirax Sarco DN40 DEP4B3 direct acting excess pressure valve having flanged PN40 connections. Note: Add suffix 'N' if the Nitrile rubber diaphragm is required. i.e. DEP4B3N.

4.6 89

TI-P206-01 CTLS Issue 13

Page 13 of 13

DEP4 Cast Steel Excess Pressure Valve