Product Handbook 2026 - Volume 1

44

Control systems Safety valves

Capacity Table - Steam - 3% Overpressure - kg/h

Orifice Designation / Current Area (cm²)

Set pressure (bar g)

J

K

L

M

N

P

Q

R

8.867

12.69

19.71

24.81

29.90

44.06

76.20

110.47

1.0

857

1226

1904

2397

2888

4256

7361

10671

1.5

1055

1511

2346

2953

3559

5245

9070

13150

2.0

1254

1795

2788

3510

4230

6233

10780

15628

2.5

1453

2080

3231

4066

4901

7222

12489

18106

3.0

1652

2365

3673

4623

5571

8210

14199

20585

3.5

1851

2649

4115

5180

6242

9198

15908

23063

4.0

2050

2934

4557

5736

6913

10187

17618

25541

4.5

2249

3219

4999

6293

7584

11175

19327

28019

5.0

2452

3509

5450

6860

8268

12183

21071

30547

5.5

2657

3802

5906

7434

8959

13202

22832

33100

6.0

2862

4095

6361

8007

9650

14220

24592

35652

6.5

3067

4389

6817

8580

10341

15238

26353

38205

4.7 6

7.0

3271

4682

7272

9154

11032

16256

28114

40758

7.5

3476

4975

7727

9727

11722

17274

29875

43310

8.0

3681

5268

8183

10300

12413

18292

31635

45863

8.5

3886

5562

8638

10873

13104

19310

33396

48416

9.0

4091

5855

9094

11447

13795

20328

35157

50968

9.5

4296

6148

9549

12020

14486

21346

36918

53521

10

4501

6441

10005

12593

15177

22364

38678

56073

12

5320

7614

11826

14886

17941

26437

45721

66284

14

6140

8787

13648

17180

20704

30509

52764

76494

16

6959

9960

15470

19473

23468

34581

59807

86705

18

7779

11133

17292

21766

26231

38654

66850

96915

20

8599

12306

19113

24059

28995

42726

73893

107126

20.7

8885

12716

19751

24862

29962

44152

76358

110699

For sizing using current areas (ASME), the discharge coefficient K for steam is 0.853.