Product Handbook 2026 - Volume 1

44

Control systems Safety valves

Table 2 - SV615 flow capacity for air in litres per second (normal I/s) at 0 °C and 1.013 bar a (calculated in accordance with EN ISO 4126:2004 at 10% overpressure) Derated coefficient of discharge (Kdr) = 0.71

Valve size DN in/out

15/20

20/32

25/40

32/50

40/65

50/80

Flow area (mm 2 )

113

314

452

661

1 075

1 662

Set pressure (bar g)

Flow capacity for air I/s

0.5

24

67

97

142

230

356

1.0

33

91

131

191

311

481

1.5

41

115

165

241

392

606

2.0

50

138

199

291

473

732

3.0

67

186

267

391

635

982

4.0

84

233

335

490

797

1 233

5.0

101

280

403

590

959

1 483

6.0

118

328

472

690

1 121

1 734

7.0

135

375

540

789

1 283

1 984

8.0

152

422

608

889

1 446

2 235

4.7 34

9.0

169

470

676

988

1 608

2 485

10.0

186

517

744

1 088

1 770

2 736

11.0

203

564

812

1 188

1 932

2 986

12.0

220

612

880

1 287

2 094

3 237

13.0

237

659

948

1 387

2 256

3 487

14.0 16.0 18.0

254

706

1 017

1 487

2 418

3 738

288

801

1 153

1 686

322

896

1 289

1 885

TI-P316-01 CTLS Issue 20

Page 6 of 10

SV615 Safety Valve

Powered by