Product Handbook 2026 - Volume 1

44

Control systems Safety valves

Table 4 - SV615 flow capacities for hot water in kilowatts (kW) at or above 100 °C (calculated in accordance with EN ISO 4126:2004) Derated coefficient of discharge (Kdr) = 0.52

Valve size DN in/out

15/20

20/32

25/40

32/50

40/65

50/80

Flow area (mm 2 )

113

314

452

661

1 075

1 662

Set pressure (bar g)

Flow capacity for hot water kW

0.5

29.96

83.26

119.86

175.27

285.06

440.71

1.0

40.60

112.81

162.39

237.47

386.21

597.09

1.5

51.23

142.36

204.92

299.66

487.36

753.47

2.0

61.86

171.96

247.45

361.86

588.51

909.86

3.0

83.13

230.99

332.51

486.24

790.81

1 222.62

4.0

104.39

290.08

417.57

610.63

993.11

1 535.38

5.0

125.66

349.17

502.63

735.02

1 195.42

1 848.15

6.0

146.92

408.26

587.69

859.41

1 397.72

2 160.91

7.0

168.19

467.36

672.75

983.80

1 600.12

2 473.67

8.0

189.45

526.45

757.81

1 108.18

1 802.32

2 786.43

4.7 36

9.0

210.72

585.54

842.88

1 232.57

2 004.62

3 099.20

10.0

231.98

644.63

927.94

1 356.96

2 206.92

3 411.96

11.0

253.25

703.72

1 013.00

1 481.35

2 409.22

3 724.72

12.0

274.51

762.81

1 098.06

1 605.74

2 611.52

4 037.49

13.0

295.78

821.90

1 183.12

1 730.12

2 813.82

4 350.25

14.0 16.0 18.0

317.04

880.99

1 268.18

1 854.51

3 016.12

4 663.01

359.58

999.17

1 438.30

2 103.29

402.11

1 117.36

1 608.42

2 352.06

Sizing and selection Refer to:- http://www.spiraxsarco.com/prs/product-sizing.asp

TI-P316-01 CTLS Issue 20

Page 8 of 10

SV615 Safety Valve