Compressed air products Isolation valves, drain traps and ancillaries
5
Pressure/temperature limits
Pressure bar g
The product must not be used in this region.
Body design conditions
PN63
63 bar g @ 120 ° C
PMA Maximum allowable pressure
400 ° C @ 42 bar g
TMA Maximum allowable temperature
0 ° C
Minimum allowable temperature
63 bar g @ 120 ° C
PMO Maximum operating pressure for saturated steam service
400 ° C @ 42 bar g
TMO Maximum operating temperature
0 ° C
Minimum operating temperature
PMOB Maximum backpressure should not exceed 80% of the inlet pressure under any conditions of operation otherwise the trap may not shut-off.
Minimum operating differential pressure for satisfactory operation
0.25 bar
5.5 2
Designed for a maximum cold hydraulic test pressure of:
95 bar g
9.5.3
TI-P610-05 CMGT Issue 12
Page 2 of 5
Airodyn Compressed Air Drain Trap