Pressure/temperature limits

0 100 200 300 400

A,D

C

B

D

0

10

20

30

40

Pressure bar g

The product must not be used in this region.

A - B Flanged EN 1092-1 PN40 and ASME 300. A - C Flanged JIS/KS 20K. D - D Flanged ASME 150.

Body design conditions

PN40

PMA Maximum allowable pressure

40 bar g @ 120 ° C

TMA Maximum allowable temperature

400 ° C @ 20 bar g

Minimum allowable temperature

0 ° C

PMO Maximum operating pressure for saturated steam service

40 bar g @ 120 ° C

TMO Maximum operating temperature

400 ° C @ 20 bar g

5.5 49

Minimum operating temperature

0 ° C

D PMX Maximum differential pressure bar, depending on the specific gravity of the liquid being drained: Specific gravity 1.0 0.9 0.8 0.7

Min. 0.6

CA44S-4.5 CA44S-10 CA44S-14

4.5

4.5

4.5

3.4

2.0

10.0

9.5

6.8

5.5

3.4

14.0

14.0

11.0

8.0

5.0

CA44S-21

21.0

19.0

15.0

10.0

6.5

32.0

30.0

30.0

16.5

10.0

CA44S-32

0.1 bar

D PMX Maximum operating temperature

PN40

60 bar g

ASME 300

60 bar g

9.5.44

Designed for a maximum cold hydraulic test pressure of:

ASME 150 30 bar g JIS/KS 20K 49 bar g