Heat transfer solutions Heat exchangers
6
Dimensions (approximate) in mm (inches)
H
6.2 16
W
L
Heat load (kW)
Type
Valve actuation
Maximum dimensions
Piping connections DN
Steam
Condensate
Min
Max
H
L
W
Pump trap Steam trap
1324 (52.1) 1344 (54.3) 1378 (54.3) 1381 (54.4) 1382 (54.4) 1460 (57.5)
1625 (64.0) 1635 (64.4)
EHHSC1
50
191
EL and PN
DN25 (1")
EHHSC2
191
299
EL and PN
DN40 (2½")
10.2.15
EHHSC3
299
640
EL and PN
825 (32.5)
DN50 (2")
1625 (64.0)
EHHSC4
640
753
EL and PN
DN40 (2½")
EHHSC5
753
815
EL and PN
DN50 (2")
1675 (65.9)
EHHSC6
-
-
EL and PN
Notes:
1. The height of the system will increase by 25 mm (1") if the wheels are fitted. 2. The heat load has been based on a steam inlet pressure of 5 bar g and 1 bar (72.5 psi g and 14.5 psi g) backpressure (50 kPa pressure drop).
TI-P481-11 CTLS Issue 3
Page 4 of 6
Spirax EasiHeat TM HTG (Steam Side Control) EN Heating System Compact Heat Transfer Solution