For alternative sizes to the standard DN40 (1½")

4. Selection of the actuator + valve adaptor The actuator has to be capable of shutting off against the maximum feedpump pressure when the boiler is not under pressure. Select the actuator from the table below: Metal Seat (T, S or W) PEEK Seat (P or C) At Feedwater temperature >50°C body rating must be considered Feedwater temperature ≤100°C Feedwater temperature >100°C

AEL72211JXA (0.4 mm/s) AEL72211GXA (0.4 mm/s) AEL72213FXA (0.4 mm/s)

AEL72211JXA (0.4 mm/s) AEL72211GXA (0.4 mm/s) AEL72213FXA (0.4 mm/s) AEL72224KXA

220/240 Vac AEL73221JXA

AEL73221JXA

110 Vac AEL73222GXA

AEL73222GXA

Actuator Type

2.3 92

24 Vac AEL73223FXA

AEL73223FXA

24 Vdc AEL73224KXA AEL72224KXA

AEL73224KXA

Size

Kv value

Maximum feedpump pressure bar g

36.0

29.1

(26.5)

11.5

(8.8)

32.2

(29.6)

14.6

(12.0)

25.0

37.1

(33.8)

15.0

(11.7)

18.0

(15.3)

DN50 Valve Size

16.0

(33.0)

40.0

(40.0)

40.0

(40.0)

40.0

19.0

(19.0)

10.0

(40.0)

16.0

(33.0)

40.0

(40.0)

10.0

DN32 Valve Size

40.0

(40.0)

40.0

19.0

(19.0)

6.3

(40.0)

N/A

N/A

4.0

10.0

40.0

(40.0)

6.3 4.0 1.6 6.3 4.0 1.6 1.0 4.0 1.6 1.0

DN25 Valve Size

40.0

(40.0)

40.0

(40.0)

19.0

(19.0)

N/A

N/A

DN20 Valve Size

40.0

(40.0)

40.0

(40.0)

N/A

N/A

19.0

(19.0)

DN15 Valve Size

40.0

(40.0)

40.0

(40.0)

N/A

N/A

19.0

(19.0)

Auxiliary Switch

AEL7X010

Valve adaptor

Integral

Mounting flange

EL5970

Spindle speed 0.8mm/s unless otherwise statedFigures in brackets denotes the differential pressures for valves fitted with high temperature graphite stem sealing. These valves have a suffix 'H'. Valve stroke is 20 mm.

TI-S75-11 EMM Issue 5

Page 6 of 7

Selection of Modulating Feedwater Valves Electrically Actuated