Product Handbook 2026 - Volume 1

Boiler house TDS blowdown controls

2

Pressure/temperature limits – BCV6_

Body design conditions:

PN40, JIS / KS 20K

ASME class 150, class 300

EN

PN40

40 bar g @ 100 °C

580 psi g @ 212 °F

ASME 150

19.0 bar g @ 38 °C

275 psi g @ 100 °F

ASME

PMA Maximum allowable pressure

ASME 300

49.6 bar g @ 38 °C

719 psi g @ 100 °F

JIS / KS

JIS / KS 20K

34 bar g @ 120 °C

493 psi g @ 248 °F

EN

PN40

400 °C @ 27.4 bar g

752 °F @ 397 psi g

ASME 150

538 °C @ 1.4 bar g

1 000 °F @ 20 psi g

ASME

TMA Maximum allowable temperature

ASME 300

538 °C @ 25.2 bar g

1 000 °F @ 365 psi g

JIS / KS

JIS / KS 20K

425 °C @ 20 bar g

797 °F @ 290 psi g

2.4 12

EN

PN40

-10 °C

14 °F

ASME 150

-29 °C

-20 °F

ASME

Minimum allowable temperature

ASME 300

-29 °C

-20 °F

JIS / KS

JIS / KS 20K

-10 °C

14 °F

EN

PN40

32.2 bar g @ 240 °C 467 psi g @ 464 °F

ASME 150

13.8 bar g @ 197 °C 200 psi g @ 386 °F

Maximum operating pressure for saturated steam service

ASME

PMO

ASME 300

33.8 bar g @ 242 °C 490 psi g @ 467 °F

JIS / KS

JIS / KS 20K

30.6 bar g @ 236 °C 443 psi g @ 456 °F

EN

PN40

400 °C @ 27.4 bar g

797 °F @ 397 psi g

ASME 150

538 °C @ 1.4 bar g

1 000 °F @ 20 psi g

ASME

TMO Maximum operating temperature

ASME 300

538 °C @ 25.2 bar g

1 000 °F @ 365 psi g

JIS / KS

JIS / KS 20K

425 °C @ 20 bar g

797 °F @ 290 psi g

EN

PN40

-10 °C

14 °F

ASME 150

-29 °C

-20 °F

ASME

Minimum operating temperature

ASME 300

-29 °C

-20 °F

JIS / KS

JIS / KS 20K

-10 °C

14 °F

Designed for a maximum cold hydraulic test pressure of:

1.5 x PMA of the relative end connection of choice

TI-P403-102 EMM Issue 9

Page 6 of 12

BCV Blowdown Control Valves DN15 to DN50 (½" to 2")