Product Handbook 2026 - Volume 1

Boiler house TDS blowdown controls

2

Pressure/temperature limits – BCV7_

PN25

ASME class 125 or ASME class 250

Body design conditions:

JIS / KS 10K

EN

PN25

25.0 bar g @ 120 °C

362 psi g @ 248 °F

ASME 125

11.5 bar g @ 140 °C

166 psi g @ 284 °F

ASME

PMA Maximum allowable pressure

ASME 250

26.7 bar g @ 140 °C

387 psi g @ 284 °F

JIS / KS

JIS / KS 10K

13.7 bar g @ 120 °C

198 psi g @ 248 °F

EN

PN25

300 °C @ 20 bar g

572 °F @ 290 psi g

ASME 125

232 °C @ 8.6 bar g

449 °F @ 125 psi g

ASME

TMA Maximum allowable temperature

ASME 250

232 °C @ 17.2 bar g

449 °F @ 249 psi g

2.4 14

JIS / KS

JIS / KS 10K

300 °C @ 9.8 bar g

572 °F @ 290 psi g

EN

PN25

-10 °C

14 °F

ASME 125

-29 °C

-20 °F

ASME

Minimum allowable temperature

ASME 250

-29 °C

-20 °F

JIS / KS

JIS / KS 10K

-10 °C

14 °F

EN

PN25

22.5 bar g @ 220 °C

326 psi g @ 428 °F

ASME 125

10.0 bar g @ 184 °C

145 psi g @ 363 °F

Maximum operating pressure for saturated steam service

ASME

PMO

ASME 250

18.0 bar g @ 209 °C

261 psi g @ 408 °F

JIS / KS

JIS / KS 10K

12.3 bar g @ 191 °C

178 psi g @ 376 °F

EN

PN25

300 °C @ 20.0 bar g

572 °F @ 290 psi g

ASME 125

232 °C @ 8.6 bar g

449 °F @ 125 psi g

ASME

TMO Maximum operating temperature

ASME 250

232 °C @ 17.2 bar g

449 °F @ 249 psi g

JIS / KS

JIS / KS 10K

300 °C @ 9.8 bar g

572 °F @ 290 psi g

EN

PN25

-10 °C

14 °F

ASME 125

-29 °C

-20 °F

ASME

Minimum operating temperature

ASME 250

-29 °C

-20 °F

JIS / KS

JIS / KS 10K

-10 °C

14 °F

Designed for a maximum cold hydraulic test pressure of:

1.5 x PMA of the relative end connection of choice

TI-P403-102 EMM Issue 9

Page 8 of 12

BCV Blowdown Control Valves DN15 to DN50 (½" to 2")