Product Handbook 2026 - Volume 1

Boiler house Bottom blowdown systems

2

BBV63 Pressure/temperature limits - EN 1092

A

L

Steam saturation curve

L

10

30

Pressure bar g

The product must not be used in this region. An extended cover is required for use in this region.

2.11 7

High temperature packing required for use in this region.

Notes: 1. Where the process fluid temperature is sub-zero and the ambient temperature is below +5 °C, the external moving parts of the valve and actuator must be heat traced to maintain normal operation. 2. When selecting a valve with a bellows scaled bonnet, the pressure/temperature limits of the bellows must be read in conjunction with the valve pressure/temperature limits shown in table below.

Body design conditions

PN40

PMA Maximum allowable pressure

40 bar g @ 100 °C

PMO Maximum operating pressure TMA Maximum allowable temperature

400 °C @ 27.4 bar g

A - L - L PN40

Minimum allowable temperature

-29 °C

Standard packing PTFE chevron (P)

250 °C @ 31.8 bar g

TMO Maximum operating temperature

High temperature packing (H)

400 °C @ 27.4 bar g

Minimum operating temperature

-29 °C

Design for a maximum cold hydraulic test pressure of:

60 bar g

TI-P405-51 EMM Issue 6

Page 7 of 11

BBV Automatic or Manually Actuated Boiler Blowdown Valves DN15 to DN50

Powered by