M610 Series II DP Transmitter Assembly

Description The M610 Series II DP transmitter assembly is designed to accept a differential pressure input from a primary flow element such as an orifice plate or Gilflo flowmeter and convert it into an analogue 4 - 20 mA output signal. The standard version comes with digital communications in the form of HART ® 5.2 which is superimposed on the 4 - 20 mA output. The 3-way manifold which is supplied already assembled to the DP transmitter acts as a means of secondary isolation and as a pressure equalisation valve to check the zero of the DP transmitter. The M610 Series II DP transmitter assembly consists of two items: - A high accuracy (0.1%) differential pressure transmitter. - A 3-way carbon steel isolation manifold. Note : These items are supplied already assembled. Pipe connections The process ports on the 3-way manifold are threaded ½ " NPT at 54 mm centres. Electrical connections ½" NPT x 1.5 screwed terminals (M20 adaptor supplied). M610 Series II technical data

3.2 38

0 - 1 326 mm (0 - 52.2”) H 2 O (0 -13 kPa) minimum 0 - 13 256 mm (0 - 522”) H 2 O (0 -130 kPa) maximum

Span

Output

4 - 20 mA dc and HART ® protocol 5.2

16 V to 45 Vdc (for non-certified application) 16 V to 28 Vdc (for E Ex ia 11c T4/T5)

Power supply

Pressure limits

-1 to 140 bar g (-14.5 to 2030 psi g)

- 40 °C to + 85 °C (-40 °F to +185 °F) (ambient for non-certified application) - 40 °C to + 100 °C (-40 °F to +212 °F) (process) ± 0.1% of calibrated span to include effects of linearity, hysteresis and repeatability Body - Stainless steel Diaphragm - Austenitic stainless steel 316L 3-way manifold - Carbon steel Fluid fill - Silicone oil ATEX Ex II 1GD - E EX ia 11c T4/T5 Ga Ex ia 111C T100 °C/T135 °C Da

Temperature limits

Accuracy

Materials of construction

Intrinsic safety

Note: If HART ® communications are required in intrinsically safe applications, barriers must be used which are designed to pass the HART ® signal.

Enclosure rating

IEC IP67 (NEMA 6 / 6P)

EMC emissions and immunity

To BS EN 61326:1997