Product Handbook 2026 - Volume 1

Flowmetering Vortex flowmeters 3

Typical Metric flowrates are on page 7

Typical Imperial flowrates - VIM20 Saturated steam (lb / h)

Nominal Pipe Size

Pressure

3"

6"

8"

12"

16"

24"

Minimum

205

800

1 385

3 099

4 893

11 132

5 psi g

Maximum

2 721

10 633

18 412

41 196

65 039

147 954

Minimum

468

1 831

3 170

7 092

11 197

25 472

100 psi g

Maximum

14 246

55 674

96 407

215 703

340 546

774 698

Minimum

632

2 471

4 278

9 572

15 111

34 377

200 psi g

Maximum

25 948

101 405

175 595

392 880

620 268

1 411 029

Minimum

762

2 976

5 153

11 530

18 203

41 410

3.6 8

300 psi g

Maximum

37 652

147 145

254 799

570 093

900 047

2 047 489

Minimum

873

3412

5 908

13 219

20 870

47 477

400 psi g

Maximum

49 494

193 420

334 930

749 382

1 183 103

2 691 404

Minimum

974

3 805

6 588

14 741

23 272

52 942

500 psi g

Maximum

61 543

240 507

416 468

931 816

1 471 125

3 346 615

Air (SCFM) at 70 °F

Nominal Pipe Size

Pressure

3"

6"

8"

12"

16"

24"

Minimum

56

220

381

852

1 345

3 059

5 psi g

Maximum

924

3 611

6 253

13 991

22 089

50 250

Minimum

157

615

1 065

2 383

3 763

8 560

100 psi g

Maximum

7 236

28 279

48 969

109 564

172 977

393 500

Minimum

216

843

1 460

3 266

5 156

11 729

200 psi g

Maximum

13 588

53 101

91 950

205 732

324 804

738 886

Minimum

262

1 022

1 770

3 960

6 251

14 221

300 psi g

Maximum

19 974

78 059

135 169

302 430

477 467

1 086 176

Minimum

301

1 175

2 034

4 551

7 186

16 346

400 psi g

Maximum

26 391

103 136

178 593

39 9588

630 859

1 435 121

Minimum

335

1 310

2 269

5 077

8 015

18 233

500 psi g

Maximum

32 834

128 314

22 2191

49 7136

784 865

1 785 464