Product Handbook 2026 - Volume 1

Control systems Control valves

4

2 Stage Perforated Trim (continued)

Kv (Cv US) values For conversion: Cv (UK) = Kv x 0.963

DN32 (1¼")

DN40 (1½")

DN50 (2")

DN65 (2½")

DN80 (3")

DN100 (4")

DN125 (5")

DN150 (6")

DN200 (8")

DN250 (10")

DN300 (12")

Trim

Full port Equal percentage

16 (18.5)

16 (18.5)

16 (18.5)

44 (51)

44 (51)

63 (73)

125 (145)

160 (185)

280 (324)

305 (353)

386 (446)

Full port Linear

16 (18.5)

16 (18.5)

16 (18.5)

50 (58)

50 (58)

63 (73)

125 (145)

160 (185)

280 (324)

305 (353)

436 (504)

Reduction 1 Equal percentage and Linear Reduction 2 Equal percentage and Linear Reduction 3 Equal percentage and Linear Reduction 4 Equal percentage and Linear Reduction 5 Equal percentage and Linear Reduction 6 Equal percentage and Linear

10 (11.6)

10 (11.6)

10 (11.6)

36 (42)

36 (42)

36 (42)

100 (116)

100 (116)

160 (185)

280 (324)

305 (353)

6.3 (7.3)

6.3 (7.3)

6.3 (7.3)

25 (29)

25 (29)

25 (29)

63 (73)

63 (73)

100 (116)

160 (185)

280 (324)

4.1 109

4 (4.6)

4 (4.6)

4 (4.6)

16 (18.5)

16 (18.5)

16 (18.5)

36 (42)

36 (42)

63 (73)

100 (116)

160 (185)

10 (11.6)

10 (11.6)

10 (11.6)

25 (29)

36 (42)

63 (73)

100 (116)

6.3 (7.3)

6.3 (7.3)

36 (42)

63 (73)

36 (42)

TI-S24-59 CTLS Issue 7

Page 11 of 14

Balanced and Multi-stage Trim Options for Spira-trol TM Two-port Control Valves