Product Handbook 2026 - Volume 1

Control systems Control valves

4

3 Stage Low Noise Trim (continued)

Kv (Cv US) values For conversion: Cv (UK) = Kv x 0.963

DN32 (1¼")

DN40 (1½")

DN50 (2")

DN65 (2½")

DN80 (3")

DN100 (4")

DN125 (5")

DN150 (6")

DN200 (8")

DN250 (10")

DN300 (12")

Trim

Full port Equal percentage

13 (15)

13 (15)

13 (15)

25 (29)

25 (29)

36 (42)

78 (90)

100 (116)

180 (208)

223 (258)

282 (326)

Full port Linear

13 (15)

13 (15)

13 (15)

25 (29)

25 (29)

36 (42)

78 (90)

100 (116)

180 (208)

282 (326)

319 (369)

Reduction 1 Equal percentage and Linear Reduction 2 Equal percentage and Linear Reduction 3 Equal percentage and Linear Reduction 4 Equal percentage and Linear Reduction 5 Equal percentage and Linear

10 (11.6)

10 (11.6)

10 (11.6)

16 (18.5)

16 (18.5)

25 (29)

63 (73)

63 (73)

160 (185)

180 (208)

223 (258)

6.3 (7.3)

6.3 (7.3)

6.3 (7.3)

10 (11.6)

10 (11.6)

16 (18.5)

36 (42)

36 (42)

100 (116)

160 (185)

180 (208)

4 (4.6)

4 (4.6)

4 (4.6)

6.3 (7.3)

6.3 (7.3)

10 (11.6)

25 (29)

25 (29)

36 (42)

100 (116)

160 (185)

4.1 111

4 (4.6)

4 (4.6)

6.3 (7.3)

16 (18.5)

36 (42)

100 (116)

10 (11.6)

36 (42)

TI-S24-59 CTLS Issue 7

Page 13 of 14

Balanced and Multi-stage Trim Options for Spira-trol TM Two-port Control Valves

Powered by