Boiler house Level controls
2
Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without notice. © Copyright 2021
AI-P693-30 EMM Issue 1
LCSR1000 Level Control Systems - Chamber Mounted
Installation and testing of on/off boiler water level controls in external chambers
Typical installation Warning: This document does not contain sufficient information to install the system safely. See the Installation and Maintenance Instructions supplied with the products for full details. LCSR1000 boiler level control systems are suitable for automatically controlled steam boilers and provide the control and alarm functions specified by HSE/CEA/SAFed Guidance BG01 arrangement 1. The LCSR1000 systems require daily manual testing as specified in BG01 and a competent boiler operator should be on site at all times the boiler is in operation. The level controls and level alarms are probably the most important controls on the boiler for ensuring safety and should only be installed and maintained by suitably trained personnel. Spirax Sarco can install, commission and provide a regular maintenance service.
2.3 5
LCS1350
LCS1350
LP11-4 probe
LP11-4 probe
Boiler
Chamber
Not used
Not used
High alarm Pump off Pump on 1st low 2nd low
Sequencing purge valves
To drain tundish or blowdown vessel