Product Handbook 2026 - Volume 1

Boiler house Level controls

2

Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without notice. © Copyright 2021

AI-P693-30 EMM Issue 1

LCSR1000 Level Control Systems - Chamber Mounted

Installation and testing of on/off boiler water level controls in external chambers

Typical installation Warning: This document does not contain sufficient information to install the system safely. See the Installation and Maintenance Instructions supplied with the products for full details. LCSR1000 boiler level control systems are suitable for automatically controlled steam boilers and provide the control and alarm functions specified by HSE/CEA/SAFed Guidance BG01 arrangement 1. The LCSR1000 systems require daily manual testing as specified in BG01 and a competent boiler operator should be on site at all times the boiler is in operation. The level controls and level alarms are probably the most important controls on the boiler for ensuring safety and should only be installed and maintained by suitably trained personnel. Spirax Sarco can install, commission and provide a regular maintenance service.

2.3 5

LCS1350

LCS1350

LP11-4 probe

LP11-4 probe

Boiler

Chamber

Not used

Not used

High alarm Pump off Pump on 1st low 2nd low

Sequencing purge valves

To drain tundish or blowdown vessel