Input signal range

4-20 mA

Impedance Air supply Air quality

Max 250 +/- 15 Ω

1.4 to 7.0 bar (regulate 0.4 to 0.7 bar above actuator spring range)

ISO 8573-1:2010 Class 3:3:2

Output pressure Actuator stroke

0 to 100% supply pressure

20 mm to 150 mm or 55° to 90°

Action

Single acting/fail vent/Double acting

Operating temperature

-20 °C to +60 °C

Air flow

80 LPM @ 1.4 bar

Steady state air consumption

2.5 LPM @ 1.4 bar

Air connections

¼ " NPT female

Single +/- 0.2% F.S. (Full Scale) Double +/- 0.5%

Sensitivity

Hysteresis

+/- 1% F.S.

Single +/- 1%F.S. Double +/- 2% F.S.

Linearity

4.4 32

Repeatability

+/- 0.5% F.S

Electrical connections Degree of protection

Cable gland M20 internal, terminals for conductors from 0.5 to 2.5 mm 2 wire

IP66

Characteristic

Linear

Linear 3.0 kg (positioner only) Mounting Kits for Linear EY3 and EY4 - 1.3 kg, UY1,2,3 - 0.9 kg, UBC - 0.2 kg Rotary 4.4 kg (Positioner and mounting kit)

Shipping weight

Positioner options Basic model

EP6

Aluminium enclosure

S D A

Single acting

Acting type

Double acting

Single Acting + Reduced Orifice Ø 1

L

Linear - See page 4 for Mounting Kit selection

Mounting type

R S A C M

Rotary - Mounting Kit included

Safe Area

Flameproof Ex d (UKEX, ATEX, IECEx, KCs)

Hazardous area protection

Flameproof Ex d (CCC, NEPSI, UKEX, ATEX, IECEx )

Flameproof Ex d (INMETRO)

Electrical and Air connection

1

M20 -¼” NPT

A B

Standard model

Non standard features

Standard Model + Supply Pressure Gauge