UK Product Handbook 2026 - Volume 1

44

Control systems Self-acting controls

Valve selection data Table 6 Normally closed valves for cooling applications For pressure temperature relationships please refer to the pressure/temperature charts in Table 4, page 6. Gunmetal

Size and pipe connections

Control system options

Valve model

Screwed BSP/NPT

Flanged PN25/ANSI 150

Body design rating

Balanced Kvs Maximum  P (bar)

Stroke mm

SA121 SA122 SA128

BMF2

½" ½" ¾"

PN25

0.59

10.3

3.2

PN25

2.58

12.0

3.2

SBRA Optional bleed available

PN25

3.86

7.0

4.0

1 "

PN25

6.80

4.7

5.0

2 ½"

DN65

PN25

65.00

2.7

9.5

NRSA Double seated valve KY51* Balanced by phosphor bronze bellows. Optional bleed available

3"

DN80

PN25

94.00

2.0

9.5

1 ¼"

PN25

16.48

9.0

8.0

1 ½"

PN25

23.70

8.2

9.0

4.5 10

2 "

PN25

34.00

6.9

9.5

Cast iron

Size and pipe connections

Control system options

Valve model

Screwed BSP/NPT

Flanged PN16

Body design rating

Balanced Kvs Maximum  P (bar)

Stroke mm

SA121 SA122 SA128

BMFRA

½" ½"

PN16

0.59

10.3

3.2

DN15

PN16

2.90

12.0

3.2

¾"

DN20

PN16

4.64

7.0

4.0

KX31 Screwed and KX33 flanged. Optional bleed available

1 "

DN25

PN16

9.80

3.5

5.6

1 ¼" 1 ½"

DN32

PN16

16.48

2.3

8.0

DN40

PN16

23.70

1.7

9.0

2 "

DN50

PN16

34.00

1.1

9.5

* Please note: The KY51 can also be used on water applications where high  P conditions exist.

Cast carbon steel

Size and pipe connections

Control system options

Body design rating

Maximum  P (bar)

Stroke mm

Valve model

Flanged

Balanced Kvs

SA121 SA122 SA128

PN25

PN40

BMRA

DN15

PN25

0.59

10.3

3.2

TI-S21-07 CTLS Issue 6

Page 10 of 13

2-Port Self-acting Temperature Control Valve Selection for Heating and Cooling Applications

Powered by