UK Product Handbook 2026 - Volume 1

44

Control systems Self-acting controls

Pressure/temperature limits

Steam saturation curve

Pressure bar g

The product must not be used in this region.

Body design conditions

PN16

16 bar g @ 120 ° C

Maximum design pressure

220 ° C @ 13.8 bar g

Maximum design temperature

-10 ° C

Minimum design temperature

220 ° C

Maximum operating temperature

0 ° C

Minimum operating temperature

Note: For lower operating temperatures consult Spirax Sarco

4.5 28

Size

DN15

DN20

DN25

DN32

DN40

DN50

KA31

13.0

10.3

4.5

3.0

2.0

1.5

KA33

13.0

10.3

4.5

3.0

2.0

1.5

Maximum differential pressure bar

KB31

10.3

9.0

8.2

6.9

KB33

10.3

9.0

8.2

6.9

Designed for a maximum cold hydraulic test pressure of:

24 bar g

Kv values Size

DN15

DN20

DN25

DN32

DN40

DN50

For conversation Cv (UK) = Kv x 0.963 Cv (US) = Kv x 1.156

KA31, KA33

2.90

4.64

9.80

16.48

23.70

34.00

KB31, KB33

9.80

16.48

23.70

34.00

Capacities For saturated steam sizing capacities see TI-GCM-08. For water valve sizing capacities see TI-GCM-09.

TI-P078-02 CTLS Issue 14

Page 2 of 5

KA31, KA33, KB31 and KB33 Cast Iron Self-acting Control Valves

Powered by