Product Handbook 2026 - Volume 1

Control systems Pressure reducing/surplussing valves

4

Sizing and selection for water applications The sizing chart below can be used to determine the Kv value of the valve for water applications by plotting: - Maximum flowrate. - Maximum valve pressure drop.

Where the Kv value is known, the chart can be used to determine pressure drop across the valve for any given flowrate. Kv sizing example: Maximum flowrate 10 m 3 /h. Maximum allowable pressure drop 0.3 bar.

Draw a horizontal line A - B at 10 m 3 /h. Draw a vertical line C - D at 0.3 bar pressure drop. At intersection E , read the required Kv = 19. Valve size required DN40 having the next highest Kv of 24.

4.6 85

Example line A

Pressure drop kPa

Pressure drop m wg

Pressure drop bar

Note: The sizing chart is empirical and should not be used for critical applications.

TI-P206-01 CTLS Issue 13

Page 9 of 13

DEP4 Cast Steel Excess Pressure Valve

Powered by