Steam traps Balanced pressure
8
Pressure/temperature limits (ISO 6552)
Steam saturation curve
Pressure bar g
The product must not be used in this region. The product should not be used in this region or beyond its operating range as damage to the internals may occur.
A - B Screwed, socket weld, butt weld and flanged ANSI 300. A - C Flanged EN 1092 PN40.
A - D Flanged JIS/KS 20K. A - E Flanged ANSI 150. F - G Flanged JIS/KS 10K.
Maximum body design conditions
PN40
PMA Maximum allowable pressure
50 bar g @ 50 °C
TMA Maximum allowable temperature
400 °C @ 35 bar g
5.2.41
Minimum allowable temperature
-60 °C
PMO Maximum operating pressure for saturated steam service
32 bar g
TMO Maximum operating temperature
240 °C @ 32 bar g
Minimum operating temperature Note: For lower operating temperatures consult Spirax Sarco
0 °C
Designed for a maximum cold hydraulic test pressure of:
75 bar g
8.2 60
TI-P005-06 CMGT Issue 5
Page 2 of 5
IBPC32 Carbon Steel Balanced Pressure Thermostatic Steam Trap with Integral Spiratec Sensor