Pipeline ancillaries Strainers and filters
10
Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without notice. © Copyright 2023
TI-S60-21 CMGT Issue 3
Pressure Drop Information (Resistance to Flow of Water) for Strainers
Note : Some strainers are not available in all the sizes shown. Please refer to the relevant Technical Information (TI) sheet for the particular product to ensure that the connection size required is available.
Fig 12SG, Fig 13, Fig 14, Fig 16 and Fig 16L
Fig 12
200 000
Screwed strainers How to use:
For a given flowrate extend a horizontal line until it intersects with the diagonal that represents the strainer size and material. Drop a vertical line from this point until it reaches the pressure drop axis. This figure indicates the pressure drop in bar, e.g. 9 000 kg / h of water passing through a 1½" Fig 14 with standard screen would have a pressure drop of 0.047 bar.
100 000
50 000 40 000 30 000
20 000
10 000
9 000
Example
5 000 4 000 3 000
2 000
1 000
10.6 99
500 400 300
200
Key Screens 100 mesh or coarser
100
0.01
0.05
0.1
0.5
1
0.01
0.1
0.5
1
All screens
0.05
0.047
Pressure drop in bar
Pressure drop in bar
Screwed strainers continued on next page
TI-S60-21 CMGT Issue 3
Pressure Drop Information (Resistance to Flow of Water) for Strainers