Product Handbook 2026 - Volume 2

Steam traps Bimetallic

8

Capacities

Differential pressure psi (x 6.89 = kPa)

15 29 73 145 290 464 44

1.5

7

7232 5432 3632

Hot water capacity

1832

Cold water capacity

932 752 572 392

212

122

Differential pressure bar (x 100 = kPa)

Safety information, installation and maintenance For full details see the Installation and Maintenance Instructions (IM-P076-09) supplied with the product. Installation note: The SMC32 and SMC32Y are designed for installation in any position, horizontal or vertical. It is recommended that a non-return valve is fitted when discharging condensate into return lines where backpressure is experienced. It is also recommended that a diffuser is fitted when discharging to atmosphere. Increased backpressure will reduce the temperature of condensate discharge. For further information consult Spirax Sarco. For ease and maintenance, consideration should be given to fitting isolation valves upstream and downstream of the steam trap. Disposal These products are recyclable. No ecological hazard is anticipated with the disposal of these products, providing due care is taken.

How to order Example : 1 off Spirax Sarco ½" SMC32 carbon steel bodied maintainable bimetallic steam trap with an integral strainer screen and screwed BSP T Rp (ISO 7-1) connections.

8.3 5

TI-P076-10 CMGT Issue 9

Page 5 of 6

SMC32 and SMC32Y Carbon Steel Bimetallic Steam Traps