Pipeline ancillaries Separators and insulation jackets
10
Pressure/temperature limits (ISO 6552)
Steam saturation curve 0
Pressure psi g
145
290
435
580
725
B
C
D E F
797 572 392 212
A
32 14
C
D E
F
A
B
Pressure bar g
The product must not be used in this region.
A - A Flanged JIS/KS 10K. B - B Flanged ASME Class 150. C - C Flanged EN 1092 PN16. D - D Flanged JIS/KS 20K. E - E Flanged EN 1092 PN40. F - F Flanged ASME Class 300 screwed BSP, NPT, socket weld and butt weld.
Body design conditions
PN50 or ASME 300
PMA Maximum allowable pressure
50 bar g @ 50 °C 725 psi g @ 122 °F
TMA Maximum allowable temperature
425 °C @ 28 bar g
797 °F @ 406 psi g
Minimum allowable temperature
-10 °C
14 °F
JIS/KS 10K
9.9 bar g
144 psi g
PN16
11.4 bar g
165 psi g
ASME 150
11.4 bar g
165 psi g
7.7.38
PMO Maximum operating pressure for saturated steam service
JIS/KS 10K
23.5 bar g
341 psi g
PN40
25.8 bar g
374 psi g
ASME 300
34.1 bar g
495 psi g
Scrd/SW/BW
34.1 bar g
495 psi g
TMO Maximum operating temperature
425 °C @ 28 bar g
797 °F @ 406 psi g
Minimum operating temperature Note: For lower operating temperatures consult Spirax Sarco.
-10 °C
14 °F
JIS/KS 10K
20.6 bar g
299 psi g
10.7 33
PN16
24.0 bar g
348 psi g
ASME 150
30.0 bar g
435 psi g
Designed for a maximum cold hydraulic test pressure of:
JIS/KS 10K
50.0 bar g
725 psi g
PN40
60.0 bar g
870 psi g
ASME 300
76.6 bar g
1111 psi g
Scrd/SW/BW 1111 psi g Note: Flanged separators (S6) may be supplied with a lower pressure rating than that cast into the body. Reference should be made to the appropriate operating chart to determine the actual product limitations. 76.6 bar g
TI-P023-12 CMGT Issue 18
Page 3 of 5
S6 Austenitic Stainless Steel Separator