UK Product Handbook 2026 - Volume 2

Pipeline ancillaries Sight glasses

10

Pressure/temperature limits

A

Steam saturation curve

C

B

Pressure bar g

The product must not be used in this region.

A - B Flanged EN 1092 PN25 A - C Flanged BS 1560 ASME (ANSI) Class 150

Body design conditions

PN25 and ASME (ANSI) 150

PN25

25 bar g @ 100 °C

PMA Maximum allowable pressure

ASME 150

17.2 bar g @ 35 °C

PN25 280°C @ 18 bar g ASME 150 280°C @ 10 bar g

TMA Maximum allowable temperature

Minimum allowable temperature

-10 °C

PN25

21 bar g

PMO Maximum operating pressure for saturated steam service

ASME 150

13.8 bar g

TMO Maximum operating temperature

280 °C

Minimum operating temperature Note: For lower temperatures consult Spirax Sarco.

0 °C

PN25

38 bar g

Designed for a maximum cold hydraulic test pressure of:

ASME 150

30 bar g

7.8.15

PN25

21 bar g

PTMX Maximum test pressure (steam service)

ASME 150

13.8 bar g

10.8 14

TI-P130-01 CMGT Issue 11

Page 2 of 4

SG253 Sight Glass