Pipeline ancillaries Air vents and air eliminators
10
Dimensions/weights (approximate) in mm and kg
Withdrawal distance for seat assembly E
B
C
D
A A1
Weight Scrd/SW/BW Flgd
Size
A
A1
B
C
D
E
½" DN15
95
150
94
64
17
37
1.4
2.9
¾" DN20
95
150
94
64
19
37
1.4
3.5
1"
DN25
95
160
94
64
23
37
1.5
4.1
Safety information, installation and maintenance For full details see the Installation and Maintenance Instructions (IM-P123-17) supplied with the product. Installation note: The AVS32 is designed for installation with the capsule in a horizontal plane with the cover at the top. The AVS32 should be positioned at the highest point of the steam main or plant where the air collects. The outlet should be piped to a safe place. For ease and maintenance, consideration should be given to fitting isolation valves upstream and downstream of the air vent. The air vent must not be insulated .
Disposal This product is recyclable. No ecological hazard is anticipated with the disposal of this product, providing due care is taken.
10.11 12
How to order Example: 1 off Spirax Sarco ½ " AVS32 air vent having screwed BSP T Rp (ISO 7-1) connections.
TI-P123-16 CMGT Issue 7
Page 4 of 5
AVS32 Stainless Steel Air Vent for Steam Systems