Steam traps Ball float
8
Pressure/temperature limits (ISO 6552)
The product should not be used in this region due to the limitations of the sensor.
Pressure psi g
0
29
58
87
116 145
174 203 232
482 392 302 212 122 0
Steam saturation curve
Pressure bar g
The product must not be used in this region.
Body design conditions
PN16
PMA Maximum allowable pressure
16 bar g @ 100 °C
232 psi g @ 212 °F
TMA Maximum allowable temperature
250 °C @ 13 bar g
482 °F @ 188 psi g
Minimum allowable temperature
-10 °C
14 °F
PMO Maximum operating pressure for saturated steam service
14 bar g
203 psi g
TMO Maximum operating temperature
240 °C @ 13 bar g
464 °F @ 188 psi g
Minimum operating temperature
0 °C
32 °F
IFT14-4.5 IFT14-10 IFT14-14
4.5 bar
65 psi
10 bar
145 psi
PMX Maximum differential pressure
14 bar
203 psi
Designed for a maximum cold hydraulic test pressure of:
24 bar g
348 psi g
8.5 13
TI-P615-01 CMGT Issue 8
Page 3 of 6
IFT14 Ball Float Steam Trap with Integral Spiratec Sensor