Steam traps Ball float
8
How to order Example: 1 off Spirax Sarco DN40 IFT54H-4.5 ball float steam trap with a carbon steel body and cover having an integral sensor (SS1) to identify steam leakage. Flanged connections to EN 1092 PN40. Trap to be fitted with the optional balance and drain connections.
Safety information, installation and maintenance For full details see the Installation and Maintenance Instructions (IM-P603-03) supplied with the product. Installation note:
The trap is designed for installation with the float arm in a horizontal plane so that it rises and falls vertically, ideally with a drop leg immediately preceding the trap. Suitable isolation valves must be installed to allow for safe maintenance/replacement. Where steam traps are fitted in exposed conditions, the possibility of freezing damage may be reduced by thermal insulation/draining/isolation. Caution: The cover gasket and main valve assembly gasket may contain a thin stainless steel support ring which may cause physical injury if it is not handled and disposed of carefully. Maintenance note: Maintenance can be completed with the trap in the pipeline, once the safety procedures have been observed. It is recommended that new gaskets and spares are used whenever maintenance is undertaken.
Disposal No ecological hazard is anticipated with the disposal of these products provided due care is taken.
5.5.140
8.5 157
TI-P615-06 CMGT Issue 5
Page 5 of 6
IFT54 Carbon Steel Ball Float Steam Trap with Integral Spiratec Sensor and Flanged Connections
Powered by FlippingBook