Product Handbook 2026 - Volume 2

Steam traps Ball float

8

Sizes and pipe connections DN40 and DN50 socket weld BS 3799. DN40 and DN50 flanged EN 1092 PN100. Note: Other connections are available upon request but may limit the operating range – Please consult Spirax Sarco for further information. Drain plug connection is 3/8 " screwed BSP T Rp (ISO 7-1) as standard.

Pressure/temperature limits

Steam saturation curve

Pressure bar g

The product must not be used in this region.

Body design conditions

PN100

PMA Maximum allowable pressure

100 bar g @ 50 °C

TMA Maximum allowable temperature

425 °C @ 46 bar g

Minimum allowable temperature

-29 °C

PMO Maximum operating pressure for saturated steam service

70 bar g

TMO Maximum operating temperature

425 °C @ 46 bar g

Minimum operating temperature

0 °C

FTC80-45

45 bar

∆PMX Maximum differential pressure

FTC80-62

62 bar

FTC80-80

70 bar

Product is safe for use under full vacuum conditions Designed for a maximum cold hydraulic test pressure of

150 bar g

8.5 176

TI-P179-03 CMGT Issue 6

Page 2 of 6

FTC80 Cast Steel DN40 and DN50 Ball Float Steam Trap with EN Body