Steam traps Inverted bucket
8
Capacities - DN25 Note: IBV inverted bucket steam traps should be selected for use at the most appropriate working differential pressure and not on the basis of load. Condensate discharge capacities (kg/h) - The discharge capacities in the table are referring to the operating temperature of the saturated steam and the PMO (PS) of the steam trap shall be the relevant D P maximum differential pressure of each specific model.
a) The hourly amount of condensate to be discharged, inclusive of the safety factor: x 1.5 for continuous use, x 2 to x 3 for intermittent use. b) The effective differential pressure.
For optimum trap selection you need to know the following criteria:
Working example:
Condensate discharge = 2000 kg/h
The unit of choice would have a D P max. differential pressure of 15 bar which is greater than the upstream pressure. For full product selection and nomenclature follow the guide on page 13.
Effective differential pressure = 4 bar Upstream pressure = 5 bar g Backpressure = 1 bar g
Differential pressure psi (× 6.8 = kPa)
1012
1595
14.5
29
43
58 72 87
145
217 290
435 580 725 870
1305
13227 11023
8818
6613 5511
5.6.45
4409
3306
2204 1984 1763 1543 1322
8.6 42
1102
881
661
551
440 330 264 242 220
Differential pressure bar (x 100 = kPa)
TI-P067-10 CMGT Issue 4
Page 10 of 17
IBV Series C Carbon Steel Inverted Bucket Vertical Steam Trap