Steam traps Inverted bucket
8
Pressure/temperature limits (ISO 6552) - Screwed, Socket weld and Flanged EN1092-1 (continued)
L K
A
Steam saturation curve
L
K
Pressure bar g
The product must not be used in this region or beyond the parameter of the PMA or TMA of the relative end connection. * Please note that the PMO (PS) is limited to the maximum D P of the selected IBV.
PMA - Maximum allowable pressure
25 bar g @ 50 °C
TMA - Maximum allowable temperature
425 °C @ 11.2 bar g
Minimum allowable temperature
-46 °C
A-K-K
PN25
* PMO (PS) - Maximum operating pressure for saturated steam service
19 bar g
TMO (TS) - Maximum operating temperature for saturated steam service
212 °C @ 11.6 bar g
Designed for a maximum cold hydraulic test pressure of:
35.7 bar g
PMA - Maximum allowable pressure
16 bar g @ 50 °C
TMA - Maximum allowable temperature
425 °C @ 7.1 bar g
Minimum allowable temperature
-46 °C
A-L-L
PN16
8.6 57
* PMO (PS) - Maximum operating pressure for saturated steam service
12 bar g
TMO (TS) - Maximum operating temperature for saturated steam service
191 °C @ 7.4 bar g
Designed for a maximum cold hydraulic test pressure of:
22.8 bar g
TI-P067-13 CMGT Issue 4
Page 7 of 17
IBV Series C-LF2 Carbon Steel Inverted Bucket Vertical Steam Trap
Powered by FlippingBook