UK Product Handbook 2026 - Volume 2

Steam traps Inverted bucket

8

Pressure/temperature limits (ISO 6552) - Flanged EN1092-1

Pressure psi g

J

H

G

A

Steam saturation curve

J

H

G

-29

Pressure bar g

The product must not be used in this region or beyond the parameter of the PMA or TMA of the relative end connection.

* Please note that the PMO is limited to the maximum D P of the selected IBV.

Body design conditions

PN100

PMA - Maximum allowable pressure

100 bar g @ 50 °C

TMA - Maximum allowable temperature

538 °C @ 37.1 bar g

Minimum allowable temperature

-29 °C

A-G-G

PN100

5.6.67

* PMO - Maximum operating pressure for saturated steam service

99.4 bar g @ 311 °C

TMO - Maximum operating temperature for saturated steam service

279 °C @ 63 bar g

Designed for a maximum cold hydraulic test pressure of:

143 bar g

PMA - Maximum allowable pressure

63 bar g @ 50 °C

TMA - Maximum allowable temperature

538 °C @ 23.4 bar g

Minimum allowable temperature

-29 °C

A-H-H

PN63

8.6 74

* PMO - Maximum operating pressure for saturated steam service

63 bar g @ 279 °C

TMO - Maximum operating temperature for saturated steam service

279 °C @ 63 bar g

Designed for a maximum cold hydraulic test pressure of:

90 bar g

PMA - Maximum allowable pressure

40 bar g @ 50 °C

TMA - Maximum allowable temperature

538 °C @ 14.8 bar g

Minimum allowable temperature

-29 °C

A-J-J

PN40

* PMO - Maximum operating pressure for saturated steam service

40 bar g @ 251 °C

TMO - Maximum operating temperature for saturated steam service

251 °C @ 40 bar g

Designed for a maximum cold hydraulic test pressure of:

57.2 bar g

Pressure/temperature limits continued on next page

TI-P067-15 CMGT Issue 5

Page 6 of 17

IBV Series Z Alloy Steel Inverted Bucket Vertical Steam Trap

Powered by