Steam traps Balanced pressure
8
Maintenance See IM-P126-05 for full maintenance details Replacement of capsule assembly:
Before any maintenance is undertaken, suitable independent isolation valves should be closed and the trap positioned in the 'bypass' mode. Allow the trap to cool. Remove the cap and lift out the old capsule, spring and spacer plate. Drop in a new spacer plate, capsule and spring. Screw on the cap using a new 'O' ring assembled into the groove in the top of the cap. Always fit a completely new assembly when replacing the capsule. How to order Example: 1 off ½" Spirax Sarco BPT13 balanced pressure thermostatic steam trap with a capsule marked 'SUB' for sub-cooled operation.
Capacities
Hot water capacity
Cold water capacity
Differential pressure bar (x 100 = kPa)
8.2 18
TI-P126-03 ST Issue 6
Page 4 of 5
BPT13T and BPT13TGX Thermostatic Steam Traps