UK Product Handbook 2026 - Volume 1

Control systems Self-acting controls

4

1

Capacities

2

3 4 5

10

4 5

10

4.5 81

20

30 40 50

100

200

Example of how to use the capacities chart Where: - Example load = 20 kg/h - Upstream gauge pressure 5 bar = 6 bar abs. Method: - Draw a horizontal line from 6 bar abs. - Draw a horizontal line from 20 kg/h

- Drop a vertical line from the 6 bar x critical pressure crossing point until it crosses 20 kg/h horizontal. - The Kv for valve selection is given at this crossing point as Kv 0.3 - From the P-band table below a ¾" valve has 4 °C P-band.

Kv at P-band in °C Size 1 °C

2 °C

4 °C

6 °C

8 °C

Maximum lift K v 0.55 at 15 °C Xp

For conversion: Cv (UK) = Kv x 0.963 Cv (US) = Kv x 1.156

½" ¾"

0.18

0.22

0.27

0.29

0.32

0.20

0.23

0.29

0.29

0.33

0.87 at 15 °C Xp

Operating temperature at design Kv = Set value - Xp

TI-P350-01 CTLS Issue 5

Page 3 of 4

TA10A and TA10P Steam Tracing Temperature Control Systems