UK Product Handbook 2026 - Volume 2

Pipeline ancillaries Separators and insulation jackets

10

Pressure/temperature limits

Pressure psi g

B

C

F

D E

A

Steam saturation curve

A

C

B

F

D E

Pressure bar g

The product must not be used in this region. A - A Flanged JIS/KS 10K. B - B Flanged ASME Class 150. C - C Flanged EN 1092 PN16. D - D Flanged JIS/KS 20K. E - E Flanged EN 1092 PN40. F - F Screwed BSP, NPT, socket weld and butt weld.

Body design conditions

PN50 or ASME 300

PMA Maximum allowable pressure

50 bar g @ 50 °C

725 psi g @ 122 °F

TMA Maximum allowable temperature

425 °C @ 28 bar g

797 °F @ 406 psi g

Minimum allowable temperature

-10 °C

14 °F

JIS/KS 10K

12.5 bar g

181 psi g

PN16

13.8 bar g

200 psi g

7.7.29

ASME 150

15.0 bar g

218 psi g

JIS/KS 20K

30.0 bar g

435 psi g

PMO Maximum operating pressure for saturated steam service

PN40

35.9 bar g

521 psi g

ASME 300

41.4 bar g

600 psi g

Scrd/SW/BW

41.4 bar g

600 psi g

TMO Maximum operating temperature

425 °C @ 28 bar g

797 °F @ 406 psi g

Minimum operating temperature Note: For lower operating temperatures consult Spirax Sarco.

-10 °C

14 °F

10.7 24

JIS/KS 10K

20.6 bar g

299 psi g

PN16

24.0 bar g

348 psi g

ASME 150

30.0 bar g

435 psi g

JIS/KS 20K

50.0 bar g

725 psi g

Designed for a maximum cold hydraulic test pressure of:

PN40

60.0 bar g

870 psi g

ASME 300

76.6 bar g

1 111 psi g

Scrd/SW/BW 1 111 psi g Note: Flanged separators (S5) may be supplied with a lower pressure rating than that cast into the body. Reference should be made to the appropriate operating chart to determine the actual product limitations. 76.6 bar g

TI-P023-11 CMGT Issue 16

Page 2 of 4

S5 Carbon Steel Separator

Powered by