UK Product Handbook 2026 - Volume 2

Steam traps Thermodynamic

8

Pressure/temperature limits (ISO 6552)

Steam saturation curve

Pressure bar g

The product must not be used in this region. The sensor limits the PMA and TMA to 240 °C @ 32 bar g. *

Body design conditions

PN63

PMA * Maximum allowable pressure TMA * Maximum allowable temperature

63 bar g @ 100 °C

400 °C @ 42 bar g

Minimum allowable temperature

0 °C

PMO Maximum operating pressure

32 bar g

TMO Maximum operating temperature

240 °C @ 32 bar g

Minimum operating temperature

0 °C

ITD42L and ITD42H

0.25 bar g

Minimum inlet pressure for satisfactory operation

ITD42LA and ITD42HA

0.80 bar g

5.7.10

PMOB Maximum operating backpressure should not exceed 80% of the upstream pressure Designed for a maximum cold hydraulic test pressure of:

95 bar g

Capacities (in accordance with ISO 7842)

1000

8.7 13

500 400 300

200

100

50

2 3 4 5

0.7 1

10

20 32

Differential pressure bar (x 100 = kPa)

TI-P614-01 CMGT Issue 4

Page 3 of 5

ITD32 Thermodynamic Steam Trap with Integral Spiratec Sensor