UK Product Handbook 2026 - Volume 2

Pipeline ancillaries Strainers and filters

10

Safety information, installation and maintenance For full details see the Installation and Maintenance Instructions (IM-S60-18) supplied with the product. Installation note

The strainer should be installed in the direction of flow, as indicated on the body. On applications involving steam or gases the pocket should be in the horizontal plane. On liquid systems the pocket should point downwards. Suitable isolation valves must be installed to allow for safe maintenance and trap replacement. Maintenance note Maintenance can be completed with the strainer in the pipeline, once the safety procedures have been observed. It is recommended that a new gasket is used whenever maintenance is undertaken. Warning The strainer cap gasket contains a thin stainless steel support ring, which may cause physical injury if it is not handled and disposed of carefully. Disposal The product is recyclable. No ecological hazard is anticipated with disposal of this product, providing due care is taken.

How to order Example: 1 off Spirax Sarco DN32 Fig 36 strainer having a stainless steel screen with 0.8 mm perforations. The connections are to be flanged EN 1092 PN40.

7.6.58

10.6 71

TI-P160-02 CMGT Issue 15

Page 5 of 6

Fig 36 Austenitic Stainless Steel Strainer