Pipeline ancillaries Strainers and filters
10
Materials
1
4
5
3
2
No. Part
Material
1 2 3 4 5
Body
Austenitic stainless steel
ASTM A351 CF8M
Cap
Austenitic stainless steel
ASTM A351 CF8M
Cap gasket
Reinforced exfoliated graphite
Strainer screen
Austenitic stainless steel
ASTM A240 316L
Bolts
Austenitic stainless steel
EN ISO 3506 A2 - 70
Pressure / temperature limits
Steam saturation curve
Pressure bar g
The product must not be used in this region. Note: Special testing to allow lower temperature operation can be provided at extra cost. Consult Spirax Sarco. Body design conditions
10.6 86
ASME (ANSI) 150
PMA Maximum allowable pressure
19 bar g (275.5 psi g)
400 °C (752 ° F)
TMA Maximum allowable temperature
-29 °C (-20 ° F)
Minimum allowable temperature
PMO Maximum operating pressure for saturated steam service TMO Maximum operating temperature
400 °C (752 ° F)
-29 °C (-20 ° F)
Minimum operating temperature
Product is safe for use under full vacuum conditions Designed for a maximum cold hydraulic test pressure of:
30 bar g (435 psi g)
TI-P160-04 CMGT Issue 13
Page 2 of 4
Fig 3616 Austenitic Stainless Steel Strainer - ASTM Material